What are requirements for the coolant used in a hydro-cooling system.
whatsminer
2025.05.26
26
0

You can refer to the following content for details

If a liquid medium uses pure water + special corrosion inhibitor + antifreeze, parameters related to the liquid temperature and the liquid flow of ethylene glycol or propylene glycol solution + pure water (distilled water) + special corrosion inhibitor are shown in Table 1‑1.

Table 1‑1

Item

Coolant

Liquid temperature

Liquid flow

20 % ethylene glycol or propylene glycol solution + pure water (distilled water) + special corrosion inhibitor

Working temperature (inlet): 20 ℃ – 50 ℃ @ normal mode, 20 ℃ – 39 ℃ @ high performance mode

Inlet liquid temperature control accuracy: ± 2 ℃

Storage and transportation temperature: -40 °C – +70 ℃

Note: The liquid in the hydro-cooling miner must be emptied after storage and transportation for more than 2 hours.

Rated flow: ≥ 10.7 L/min

Flow control accuracy: ± 10 %

Note: Temperature difference between inlet liquid and outlet liquid corresponds to 10.7 L/min is close to 10 ℃ @ normal mode, and 14 ℃ @ high performance mode.

30 % ethylene glycol or propylene glycol solution + pure water (distilled water) + special corrosion inhibitor

Working temperature (inlet): 20 ℃ – 49 ℃ @ normal mode, 20 ℃ – 38.5 ℃ @ high performance mode

Inlet liquid temperature control accuracy: ± 2 ℃

Storage and transportation temperature: -40 °C – +70 ℃

Note: The liquid in the hydro-cooling miner must be emptied after storage and transportation for more than 2 hours.

Rated flow: ≥ 11 L/min

Flow control accuracy: ± 10 %

Note: Temperature difference between inlet liquid and outlet liquid corresponds to 11 L/min is close to 10 ℃ @ normal mode, and 14 ℃ @ high performance mode.

40 % ethylene glycol or propylene glycol solution + pure water (distilled water) + special corrosion inhibitor

Working temperature (inlet): 20 ℃ – 48 ℃ @ normal mode, 20 ℃ – 38 ℃ @ high performance mode

Inlet liquid temperature control accuracy: ± 2 ℃

Storage and transportation temperature: -40 °C – +70 ℃

Note: The liquid in the hydro-cooling miner must be emptied after storage and transportation for more than 2 hours.

Rated flow: ≥ 11.4 L/min

Flow control accuracy: ± 10 %

Note: Temperature difference between inlet liquid and outlet liquid corresponds to 11.4 L/min is close to 10 ℃ @ normal mode, and 14 ℃ @ high performance mode.

50 % ethylene glycol or propylene glycol solution + pure water (distilled water) + special corrosion inhibitor

Working temperature (inlet): 20 ℃ – 47 ℃ @ normal mode, 20 ℃ – 37.5 ℃ @ high performance mode

Inlet liquid temperature control accuracy: ± 2 ℃

Storage and transportation temperature: -40 °C – +70 ℃

Note: The liquid in the hydro-cooling miner must be emptied after storage and transportation for more than 2 hours.

Rated flow: ≥ 11.6 L/min

Flow control accuracy: ± 10 %

Note: Temperature difference between inlet liquid and outlet liquid corresponds to 11.6 L/min is close to 10 ℃ @ normal mode, and 14 ℃ @ high performance mode.

Initial index requirements for coolant and coolant test indicators and cycles are shown in the following tables.

Table 1‑2

Itmes

Unit

Initial indices

Test method

pH (20 ℃)

7.0 – 8.7

ASTM D1287

Total number of bacterial colonies (microorganisms)

CFU/mL

< 100

AOAC 990

Sulfate

mg/L

< 10

ASTM D5827

Chloride

mg/L

< 20

ASTM D5827

Total hardness (CaCO3)

mg/L

< 20

ASTM D1126

Conductivity (20 ℃)

μs/cm

< 2000

ASTM D1125-23

Appearance

Clear liquid without precipitation

Visual inspection

Corrosion inhibitor

100 % active ingredients

Reserve alkalinity

mL

≥ 2.0

ASTM D11221

Glassware corrosion (70 °C)

Stainless steel

mg/pcs

± 10

ASTM D1384

3003 aluminum alloy

mg/pcs

± 10

6061 aluminum alloy

mg/pcs

± 10

Non-metal compatibility/mass change

EPDM

%

± 5

ISO 1817

Fluorinated silicone rubber

%

± 5

NBR

%

± 5

Table 1‑3

Items

Unit

Detection Indices

Test cycle

Reference test methods

pH (20 ℃)*

7.0 – 8.7

Every 2 months

ASTM D1287

Total number of colonies (microorganisms)*

CFU/mL

≤ 100

Every 6 months

AOAC 990

Sulfate

mg/L

≤ 10

Every 6 months

ASTM D5827

Chloride

mg/L

≤ 20

Every 6 months

ASTM D5827

Total hardness (CaCO3)

mg/L

≤ 20

Every 6 months

ASTM D1126

Conductivity (20 ℃)*

μs/cm

Increment ≤ 1500

Every 2 months

ASTM D1125-23

Appearance*

Clear liquid without precipitation

Every 2 months

Visual inspection

Copper ions*

mg/L

Increment ≤ 0.5

Every 6 months

ASTM D1971-02

Iron ions*

mg/L

Increment ≤ 0.5

Every 6 months

ASTM D1971-02

Aluminum ions*

mg/L

Increment ≤0.5

Every 6 months

ASTM D1971-02

Corrosion Inhibitor

Active ingredients ≥ 80 %

Every 6 months

Entrust corresponding suppliers to conduct tests

Reserve alkalinity

mL

≥ 2.0

Every 2 months

ASTM D11221

Note: * indicates that this index must be checked.